The obligations under UNI 8364-3 and local regulations to prevent soil contamination
Underground tanks serving heating plants and company fuel stores age without giving any visible warning. A leak, even a small and prolonged one, means contamination of the soil and potentially of the groundwater, with remediation obligations falling on the responsible party and costs far exceeding those of preventive maintenance.
For this reason the technical and regulatory framework requires periodic checks on the state of preservation and tightness tests to verify the integrity of the structure, particularly for single-wall tanks without an interstitial space and leak detection system.
The technical standard for maintenance is UNI 8364-3, on the control and maintenance of heating systems. The intervals for tightness tests, however, do not come from a single national rule: they largely depend on the hygiene regulations of the municipality where the plant is located and, where these are absent, on the manufacturer's instructions, the guidelines of the regional environmental protection agencies and the applicable fire prevention rules. In the background stands Legislative Decree 152/2006, governing liability for contamination and remediation duties.
| Activity | Condition | Indicative interval |
|---|---|---|
| Tightness test | Tank over 30 years old, not refurbished | Yearly |
| Tank between 15 and 30 years old, not refurbished | Every 2 years | |
| Refurbished tank, from the fifth year | Every 3 years | |
| Internal cleaning and sediment removal | Tanks containing diesel fuel | 5 years |
| Internal cleaning and sediment removal | Tanks containing heavy fuel oils | 3 years |
Indicative values: the actual interval must always be checked against the municipal hygiene regulations and the local requirements applicable to the plant, which may impose shorter intervals.
Stefano Luise Engineering S.r.l. provides periodic inspections and tightness tests on underground fuel oil tanks: regulatory framing of the specific case, document review, condition inspection, tightness test with report and recommended corrective actions, through to assistance with taking the tank out of service.
UNI 8364-3 • Italian Legislative Decree 152/2006 • Municipal hygiene regulations • Regional environmental agency guidelines • Applicable fire prevention rules